catalog

POWERMATIC® YSLYCY-O 0,6/1kV without a grounding wire Power cable 0.6/1.0 kV flexible, shielded

POWERMATIC® YSLYCY-O 0,6/1kV without a grounding wire
icon_red_1

Stability during single burning

icon_red_5

Resistant to electrical influences-shielded

FIELD OF APPLICATION

  • Production of industrial machinery, heating and air conditioning equipment
  • In residential, household, administrative, industrial and other premises, if the cable is not subject to mechanical damage during operation
  • For electrical machines with alternating current
  • For fixed installation in distribution networks and industrial installations
  • For stationary applications as well as for installation with limited mobility and no tensile loads
  • In dry and wet production facilities, canals, tunnels, and on special cable racks

ADVANTAGES

  • Easy installation due to great flexibility
  • Shields protect against electromagnetic waves and absorb external electromagnetic signals

CONSTRUCTION

Resin

Copper conductors in accordance with the requirements of DSTU EN 60228, flexibility class 5

Insulation

Polyvinyl chloride plastic.

Outer shell

Polyvinyl chloride plastic, black color

Number of cores

2, 3, 4, 5, 7, 12, 18, 25

Inner shell

Polyvinyl chloride plastic.

Screen

Braid made of tinned copper wires

TECHNICAL CHARACTERISTICS

Electrical resistance depending on the rated area cross-section of the conductor, not more:

mm²
Ohm/km

0,75
26

1
19,5

1,5
13,3

2,5
7,98

4
4,95

6
3,3

10
1,91

16
1,21

25
0,78

35
0,554

Temperature range

from -40˚С to +70˚С from -5˚С to +70˚С

Temperature range:
-in fixed installation
-conditions during installation

from -40˚С to +70˚С
from -5°C to +70°C

Test voltage

4000 W

Operating voltage

600/1000 W

Electrical resistance of insulation

100 megohms/km

Minimum bending radius

20 х D 6 х D

Minimum bending radius limited mobility fixed application

20 х D
6 х D

Color identification of cores

EN 50334 DSTU HD 308 S2

COMPLIANCE / STANDARDS

DSTU IEC 60502-1

Resistance to single combustion, DSTU EN 60332-1-2

TABLE OF NOMENCLATURES

Article no. Number of cores and
cross section mm2
Maximum
outer diameter
Mass of copper Mass.
20100801 2х0,75 12.4 40.2 158
20100802 3х0,75 12.9 48.6 173
20100803 4х0,75 13.7 58.0 196
20100804 5х0,75 14.6 67.6 225
20100805 7х0,75 15.8 84.4 267
20100806 12х0,75 19.6 130.0 403
20100807 18х0,75 22.3 179.9 534
20100808 25х0,75 26.1 239.5 704
20100809 2х1 12.8 45.8 170
20100810 3х1 13.3 56.7 188
20100811 4х1 14.1 68.5 214
20100812 5х1 15.1 80.7 246
20100813 7х1 16.3 102.3 295
20100814 12х1 20.3 160.1 448
20100815 18х1 23.4 224.5 609
20100816 25х1 27.4 301.1 805
20100817 2х1,5 13.9 57.8 203
20100818 3х1,5 14.5 73.2 228
20100819 4х1,5 15.7 89.8 269
20100820 5х1,5 16.8 106.8 312
20100821 7х1,5 18 137.6 369
20100822 12х1,5 22.9 219.1 579
20100823 18х1,5 26.4 311.0 795
20100824 25х1,5 31.3 453.4 1093
20100825 3х2,5 16 104.4 289
20100826 4х2,5 17.1 130.6 337
20100827 5х2,5 18.4 157.3 396
20100828 7х2,5 20 206.9 483
20100829 12х2,5 25.4 336.2 759
20100830 4х4 20 194.4 473
20100831 5х4 21.6 235.9 561
20100832 7х4 23.5 314.6 692
20100833 4х6 21.7 273.2 592
20100834 5х6 23.8 333.8 716
20100835 4х10 24.7 434.7 828
20100836 5х10 27.1 534.6 1008
20100837 4х16 28 668.3 1148
20100838 5х16 31 858.6 1440
20100839 4х25 39.3 1113.3 1974
20100840 4х35 43 1544.3 2535