catalog

КМВеВнг-LS (JE-LiYCY-LS) 5th class of flexibility Control and data transmission cables, shielded

КМВеВнг-LS (JE-LiYCY-LS) 5th class of flexibility
icon_red_1

Stability during single burning

icon_red_2

Stability when burning in a bundle

FIELD OF APPLICATION

  • Construction, energy, industrial and transportation facilities
  • Data transmission in signaling, instrumentation and control systems, automated control systems, monitoring and special applications
  • In rooms with dry or humid environments under normal mechanical loads

ADVANTAGES

  • Flexible
  • The cables are tested for laying outside the hermetic zone in cable structures and premises of NPPs, in systems of classes 3, 4 according to NP 306.2.141-2008
  • The presence of a shield protects against electromagnetic waves
  • Additional versions: oil-resistant, armored

CONSTRUCTION

Resin

Copper stranded conductors in accordance with the requirements of DSTU EN 60228, flexibility class 5

Insulation

polyvinyl chloride plastic of reduced fire hazard

Outer shell

black polyvinyl chloride plastic with low smoke and gas emission

Number of cores

1÷61

Screen

Copper wire braid

TECHNICAL CHARACTERISTICS

Electrical resistance depending on the rated area cross-section of the conductor, not more:

mm²
Ohm/km

0,2
110

0,28
67

0,5
39

0,75
26

1,0
19,5

1,5
13,3

2,5
7,98

Temperature range

-40˚C to +70˚C

Test voltage

2000 V (2.5 mm2 - 2500 V)

Operating voltage

300/500 W

Electrical resistance of insulation

10 MOhm/km

Minimum bending radius

7,5 х D

Color identification of cores

DSTU IEC 60189-2, DIN 47100

COMPLIANCE / STANDARDS

Single combustion - clause 4.1 of DSTU 4809, DSTU EN 60332-1 -2

Combustion in bundles - clause 4.2 of DSTU 4809, DSTU EN 60332-3-22

Toxicity - p. 4.3 ДСТУ 4809

Smoke smoke - clause 4.4 of DSTU 4809

Combustion smoke - clause 4.5 of DSTU 4809, DSTU EN 61034-2

Halogens and corrosive activity - clause 4.6 of DSTU 4809, DSTU EN 60754-2

TABLE OF NOMENCLATURES

Article no. Number of cores and
cross section mm2
Maximum
outer diameter
Mass of copper Mass.
10503701 2х0,5 9.6 32.78 120
10503702 2х0,75 10.0 39.41 134
10503703 2х1 10.3 45.09 144
10503704 2х1,5 11.6 57.24 171
10503705 2х2,5 13.3 79,05 208
10503706 3х0,5 10.0 38.50 133
10503707 3х0,75 10.4 47.57 151
10503708 3х1 11.0 55.62 163
10503709 3х1,5 12.1 72.30 199
10503710 3х2,5 14.0 103.33 247
10503711 4х0,5 10.7 45.07 149
10503712 4х0,75 11.3 56.69 171
10503713 4х1 11.7 67.16 187
10503714 4х1,5 13.2 88.57 231
10503715 4х2,5 15.5 129.05 292
10503716 5х0,5 11.6 52.66 168
10503717 5х0,75 12.1 66.07 193
10503718 5х1 12.8 80.58 215
10503719 5х1,5 14.7 120.77 283
10503720 5х2,5 17.2 159.05 344
10503721 6х0,5 12.4 58.87 185
10503722 6х0,75 13.1 75.74 215
10503723 6х1 13.6 91.18 238
10503724 6х1,5 15.7 122.29 299
10503725 6х2,5 18.7 182.85 395
10503726 7х0,5 13.5 63.46 193
10503727 7х0,75 14.3 82.63 227
10503728 7х1 15.1 100.37 252
10503729 7х1,5 17.4 235.75 320
10503730 7х2,5 20.3 205.29 426
10503731 12х0,5 16.5 95.8 273
10503732 12х0,75 17.2 127.91 326
10503733 12х1 18.1 158.83 376
10503734 12х1,5 20.5 218.18 486
10503735 12х2,5 24.4 335.14 668
10503736 18х0,5 18.6 130.95 359
10503737 18х0,75 19.9 177.85 435
10503738 18х1 20.8 223.70 495
10503739 18х1,5 24.1 309.16 671
10503740 18х2,5 28.5 482.96 919
10503741 27х0,5 22.1 182.76 476
10503742 27х0,75 23.7 262.33 604
10503743 27х1 24.7 319.78 703
10503744 27х1,5 28.6 448.63 956
10503745 27х2,5 34.5 723.96 1340
10503746 36х0,5 24.7 223.08 604
10503747 36х0,75 26.2 326.22 758
10503748 36х1 27.6 415.25 875
10503749 36х1,5 32.5 586.39 1200
10503750 36х2,5 38.5 967.15 1696

similar products