catalog

КОПЕ1Ннг-HF (J-2YH-PIMF) Communication and alarm cable with improved communication characteristics, shielded, twisted pair, halogen-free

КОПЕ1Ннг-HF (J-2YH-PIMF)
icon_red_1

Stability during single burning

icon_red_2

Stability when burning in a bundle

icon_red_3

Halogen-free

icon_red_5

Resistant to electrical influences-shielded

FIELD OF APPLICATION

  • Alarm systems, access control systems, management, control, communication and telecommunication systems
  • For the transmission of low-power electrical signals
  • For installation of station equipment, for stationary installation inside buildings, structures, in dry and wet areas

ADVANTAGES

  • Shields protect against electromagnetic waves and absorb external electromagnetic signals
  • The wires have been tested for use outside the hermetic zone in cable structures of NPP premises, in systems of classes 3, 4 according to NP 306.2.141-2008
  • Additional versions: armoring, hydrophobicity, oil resistance

CONSTRUCTION

Resin

Copper conductors, in accordance with the requirements of DSTU EN 60228, flexibility class 1

Insulation

Polyethylene

Outer shell

White polyvinyl chloride plastic.

Number of cores

1÷61х2

Screen

Synthetic film foiled with aluminum + grounding conductor

Screen 1

braid of copper ("el" - tinned) wires

Screen 2

shielded pairs

TECHNICAL CHARACTERISTICS

Electrical resistance depending on the nominal diameter of the core, not more than:

mm
Ohm/km

0,4
160

0,51
110

0,8
36

1,05
24,5

1,13
18,1

1,38
12,1

1,78
7,41

Temperature range

-30˚С to +70˚С

Test voltage

2500 W

Operating voltage

72 W

Electrical resistance of insulation

500 MOhm/km

Minimum bending radius

8 х D

Color identification of cores

DSTU IEC 60189-2

Electrical capacity

56 pF/m

COMPLIANCE / STANDARDS

Single combustion - clause 4.1 of DSTU 4809, DSTU EN 60332-1 -2

Burning in bundles - p.4.2 of DSTU 4809, DSTU EN 60332-3-22.

Toxicity - p. 4.3 DSTU 4809.

Smoke smoke - clause 4.4 of DSTU 4809.

Combustion smoke - clause 4.5 of DSTU 4809, DSTU EN 61034-2.

Halogens and corrosive activity - clause 4.6 of DSTU 4809. p.4.6 DSTU 4809, DSTU EN 60754-2

TABLE OF NOMENCLATURES

Article no. Number of cores and
cross section mm2
Maximum
outer diameter
Mass of copper Mass.
10308301 1х2х0,4 4.4 3.5 16
10308302 2х2х0,4 6.9 5.89 32
10308303 3х2х0,4 7.2 8.27 40
10308304 4х2х0,4 7.4 10.66 47
10308305 5х2х0,4 8.5 13.04 60
10308306 6х2х0,4 9.6 15.43 68
10308307 8х2х0,4 12.7 20.2 81
10308308 10х2х0,4 15.3 24.97 102
10308309 14х2х0,4 16.6 29.74 116
10308310 20х2х0,4 22.1 48.82 164
10308311 1х2х0,51 4.6 4.99 19
10308312 2х2х0,51 7.3 8.87 40
10308313 3х2х0,51 7.7 12.75 50
10308314 4х2х0,51 8.0 16.62 60
10308315 5х2х0,51 9.0 20.5 73
10308316 6х2х0,51 10.3 24.38 84
10308317 8х2х0,51 13.8 32.13 104
10308318 10х2х0,51 16.6 39.89 132
10308319 14х2х0,51 18.1 47.64 151
10308320 20х2х0,51 24.1 78.66 218
10308321 1х2х0,8 5.7 10.66 30
10308322 2х2х0,8 9.3 20.2 60
10308323 3х2х0,8 9.8 29.74 78
10308324 4х2х0,8 10.1 39.28 95
10308325 5х2х0,8 11.4 48.82 116
10308326 6х2х0,8 13.2 58.35 134
10308327 8х2х0,8 17.7 77.43 166
10308328 10х2х0,8 21.6 96.51 209
10308329 14х2х0,8 23.5 115.59 242
10308330 20х2х0,8 31.7 191.91 363
10308331 1х2х1,05 6.3 17.55 41
10308332 2х2х1,05 10.5 33.98 81
10308333 3х2х1,05 10.9 50.42 105
10308334 4х2х1,05 11.4 66.85 134
10308335 5х2х1,05 13.1 83.28 168
10308336 6х2х1,05 15.1 99.72 196
10308337 8х2х1,05 20.6 132.58 249
10308338 10х2х1,05 24.5 165.45 307
10308339 14х2х1,05 27.4 198.32 365
10308340 20х2х1,05 36.9 329.79 556
10308341 1х2х1,38 7.5 29.5 60
10308342 2х2х1,38 12.7 57.89 119
10308343 3х2х1,38 13.6 86.28 161
10308344 4х2х1,38 13.7 114.66 201
10308345 5х2х1,38 16.6 143.05 252
10308346 6х2х1,38 18.3 171.43 299
10308347 8х2х1,38 24.9 228.21 376
10308348 10х2х1,38 30.4 284.98 471
10308349 14х2х1,38 33.2 341.75 552
10308350 20х2х1,38 45.0 568.84 852