catalog

КОВеВнг-LS (J-YCY-LS-PF) Communication and signaling cable, shielded, twisted pair, with low smoke and gas emission

КОВеВнг-LS (J-YCY-LS-PF)
icon_red_1

Stability during single burning

icon_red_2

Stability when burning in a bundle

icon_red_5

Resistant to electrical influences-shielded

FIELD OF APPLICATION

  • Alarm systems, access control systems, management, control, communication and telecommunication systems
  • For the transmission of low-power electrical signals
  • For installation of station equipment, for stationary installation inside buildings, structures, in dry and wet areas

ADVANTAGES

  • Shields protect against electromagnetic waves and absorb external electromagnetic signals
  • The wires have been tested for use outside the hermetic zone in cable structures of NPP premises, in systems of classes 3, 4 according to NP 306.2.141-2008
  • Additional versions: armoring, hydrophobicity, oil resistance

CONSTRUCTION

Resin

Copper conductors, in accordance with the requirements of DSTU EN 60228, flexibility class 1

Insulation

polyvinyl chloride plastic of reduced fire hazard

Outer shell

black polyvinyl chloride plastic with low smoke and gas emission

Number of cores

1÷61х2

Screen

copper wire braid

Screen 1

braid of copper ("el" - tinned) wires

Screen 2

shielded pairs

TECHNICAL CHARACTERISTICS

Electrical resistance depending on the nominal diameter of the core, not more than:

mm
Ohm/km

0,4
160

0,51
110

0,8
36

1,05
24,5

1,13
18,1

1,38
12,1

1,78
7,41

Temperature range

-30˚С to +70˚С

Test voltage

1500 W

Operating voltage

300 W

Electrical resistance of insulation

100 megohms/km

Color identification of cores

DSTU IEC 60189-2

Electrical capacity

100 pF/m

COMPLIANCE / STANDARDS

Single combustion - clause 4.1 of DSTU 4809, DSTU EN 60332-1 -2

Toxicity - p. 4.3 DSTU 4809.

Smoke smoke - clause 4.4 of DSTU 4809.

Combustion smoke - clause 4.5 of DSTU 4809, DSTU EN 61034-2.

Halogens and corrosive activity - clause 4.6 of DSTU 4809. p.4.6 DSTU 4809, DSTU EN 60754-2

TABLE OF NOMENCLATURES

Article no. Number of cores and
cross section mm2
Maximum
outer diameter
Mass of copper Mass.
10308701 1х2х0,4 4.4 20.52 53
10308702 2х2х0,4 6.9 32.74 90
10308703 3х2х0,4 7.2 36.60 102
10308704 4х2х0,4 7.4 41.55 116
10308705 5х2х0,4 8.5 46.78 136
10308706 6х2х0,4 9.6 52.12 151
10308707 8х2х0,4 12.7 59.84 172
10308708 10х2х0,4 15.3 71.50 209
10308709 14х2х0,4 16.6 80.30 234
10308710 20х2х0,4 22.1 108.13 308
10308711 1х2х0,51 4.6 23.59 58
10308712 2х2х0,51 7.3 38.87 104
10308713 3х2х0,51 7.7 44.46 120
10308714 4х2х0,51 8.0 51.30 137
10308715 5х2х0,51 9.0 58.49 159
10308716 6х2х0,51 10.3 65.79 178
10308717 8х2х0,51 13.8 76.97 209
10308718 10х2х0,51 16.6 92.71 255
10308719 14х2х0,51 18.1 105.14 287
10308720 20х2х0,51 24.1 146.31 386
10308721 1х2х0,8 5.7 31.54 76
10308722 2х2х0,8 9.3 54.78 134
10308723 3х2х0,8 9.8 66.38 159
10308724 4х2х0,8 10.1 79.48 185
10308725 5х2х0,8 11.4 92.99 217
10308726 6х2х0,8 13.2 106.64 245
10308727 8х2х0,8 17.7 129.83 288
10308728 10х2х0,8 21.6 158.50 355
10308729 14х2х0,8 23.5 183.20 403
10308730 20х2х0,8 31.7 271.71 565
10308731 1х2х1,05 6.3 40.94 92
10308732 2х2х1,05 10.5 73.58 167
10308733 3х2х1,05 10.9 92.44 198
10308734 4х2х1,05 11.4 113.09 239
10308735 5х2х1,05 13.1 134.22 286
10308736 6х2х1,05 15.1 155.52 325
10308737 8х2х1,05 20.6 193.24 394
10308738 10х2х1,05 24.5 237.45 480
10308739 14х2х1,05 27.4 276.97 556
10308740 20х2х1,05 36.9 422.86 797
10308741 1х2х1,38 7.5 55.50 118
10308742 2х2х1,38 12.7 102.70 217
10308743 3х2х1,38 13.6 133.91 268
10308744 4х2х1,38 13.7 167.19 321
10308745 5х2х1,38 16.6 201.03 386
10308746 6х2х1,38 18.3 235.06 448
10308747 8х2х1,38 24.9 297.48 543
10308748 10х2х1,38 30.4 367.42 670
10308749 14х2х1,38 33.2 431.90 773
10308750 20х2х1,38 45.0 675.74 1132