catalog

КОПЕНнг-HF (J-2Y(St)Н-PF) Communication and alarm cable with improved communication characteristics, shielded, twisted pair, halogen-free

КОПЕНнг-HF (J-2Y(St)Н-PF)
icon_red_1

Stability during single burning

icon_red_2

Stability when burning in a bundle

icon_red_3

Halogen-free

icon_red_5

Resistant to electrical influences-shielded

FIELD OF APPLICATION

  • Alarm systems, access control systems, management, control, communication and telecommunication systems
  • For the transmission of low-power electrical signals
  • For installation of station equipment, for stationary installation inside buildings, structures, in dry and wet areas

ADVANTAGES

  • Shields protect against electromagnetic waves and absorb external electromagnetic signals
  • The wires have been tested for use outside the hermetic zone in cable structures of NPP premises, in systems of classes 3, 4 according to NP 306.2.141-2008
  • Additional versions: armoring, hydrophobicity, oil resistance

CONSTRUCTION

Resin

Copper conductors, in accordance with the requirements of DSTU EN 60228, flexibility class 1

Insulation

Polyethylene

Outer shell

White polyvinyl chloride plastic.

Number of cores

1÷61х2

Screen

synthetic film foiled with aluminum + grounding conductor

Screen 1

braid of copper ("el" - tinned) wires

Screen 2

shielded pairs

TECHNICAL CHARACTERISTICS

Electrical resistance depending on the nominal diameter of the core, not more than:

mm
Ohm/km

0,4
160

0,51
110

0,8
36

1,05
24,5

1,13
18,1

1,38
12,1

1,78
7,41

Temperature range

-30˚С to +70˚С

Test voltage

2500 W

Operating voltage

72 W

Electrical resistance of insulation

500 MOhm/km

Minimum bending radius

8 х D

Color identification of cores

DSTU IEC 60189-2

Electrical capacity

56 pF/m

COMPLIANCE / STANDARDS

Single combustion - clause 4.1 of DSTU 4809, DSTU EN 60332-1 -2

Burning in bundles - p.4.2 of DSTU 4809, DSTU EN 60332-3-22.

Toxicity - p. 4.3 DSTU 4809.

Smoke smoke - clause 4.4 of DSTU 4809.

Combustion smoke - clause 4.5 of DSTU 4809, DSTU EN 61034-2.

Halogens and corrosive activity - clause 4.6 of DSTU 4809. p.4.6 DSTU 4809, DSTU EN 60754-2

TABLE OF NOMENCLATURES

Article no. Number of cores and
cross section mm2
Maximum
outer diameter
Mass of copper Mass.
10301301 1х2х0,4 4.4 3.5 16
10301302 2х2х0,4 6.9 5.89 32
10301303 3х2х0,4 7.2 8.27 40
10301304 4х2х0,4 7.4 10.66 47
10301305 5х2х0,4 8.5 13.04 60
10301306 6х2х0,4 9.6 15.43 68
10301307 8х2х0,4 12.7 20.2 81
10301308 10х2х0,4 15.3 24.97 102
10301309 14х2х0,4 16.6 29.74 116
10301310 20х2х0,4 22.1 48.82 164
10301311 1х2х0,51 4.6 4.99 19
10301312 2х2х0,51 7.3 8.87 40
10301313 3х2х0,51 7.7 12.75 50
10301314 4х2х0,51 8.0 16.62 60
10301315 5х2х0,51 9.0 20.5 73
10301316 6х2х0,51 10.3 24.38 84
10301317 8х2х0,51 13.8 32.13 104
10301318 10х2х0,51 16.6 39.89 132
10301319 14х2х0,51 18.1 47.64 151
10301320 20х2х0,51 24.1 78.66 218
10301321 1х2х0,8 5.7 10.66 30
10301322 2х2х0,8 9.3 20.2 60
10301323 3х2х0,8 9.8 29.74 78
10301324 4х2х0,8 10.1 39.28 95
10301325 5х2х0,8 11.4 48.82 116
10301326 6х2х0,8 13.2 58.35 134
10301327 8х2х0,8 17.7 77.43 166
10301328 10х2х0,8 21.6 96.51 209
10301329 14х2х0,8 23.5 115.59 242
10301330 20х2х0,8 31.7 191.91 363
10301331 1х2х1,05 6.3 17.55 41
10301332 2х2х1,05 10.5 33.98 81
10301333 3х2х1,05 10.9 50.42 105
10301334 4х2х1,05 11.4 66.85 134
10301335 5х2х1,05 13.1 83.28 168
10301336 6х2х1,05 15.1 99.72 196
10301337 8х2х1,05 20.6 132.58 249
10301338 10х2х1,05 24.5 165.45 307
10301339 14х2х1,05 27.4 198.32 365
10301340 20х2х1,05 36.9 329.79 556
10301341 1х2х1,38 7.5 29.5 60
10301342 2х2х1,38 12.7 57.89 119
10301343 3х2х1,38 13.6 86.28 161
10301344 4х2х1,38 13.7 114.66 201
10301345 5х2х1,38 16.6 143.05 252
10301346 6х2х1,38 18.3 171.43 299
10301347 8х2х1,38 24.9 228.21 376
10301348 10х2х1,38 30.4 284.98 471
10301349 14х2х1,38 33.2 341.75 552
10301350 20х2х1,38 45.0 568.84 852

similar products