catalog

SIGNALMATIC® Li2Y(St)Y-PF Data transmission cable, low frequency, shielded, twisted pair

SIGNALMATIC® Li2Y(St)Y-PF
icon_red_1

Stability during single burning

FIELD OF APPLICATION

  • For the transmission of the smallest measurement and control signals
  • For internal wiring of electronic equipment
  • In rooms with dry or humid environments under normal mechanical loads

ADVANTAGES

  • The presence of a shield reduces the impact of high-frequency electromagnetic interference

CONSTRUCTION

Resin

Copper conductors in accordance with the requirements of DSTU EN 60228, flexibility class 2

Insulation

Polyethylene

Outer shell

Polyvinyl chloride plastic

Number of cores

2,3

Screen

Aluminum foil tape, grounding conductor

TECHNICAL CHARACTERISTICS

Electrical resistance depending on the rated area cross-section of the conductor, not more:

mm²
Ohm/km

0,2
110

20/7AWG
36

Temperature range:
-in fixed installation
-conditions during installation

from -40˚С to +70˚С
from -5°C to +70°C

Test voltage

2000 V (2.5 mm2 - 2500 V)

Operating voltage

300/500 W

Electrical resistance of insulation

10 MOhm/km

Minimum bending radius

7,5 х D

Color identification of cores

DSTU IEC 60189-2

Electrical capacity

120 pF/m

COMPLIANCE / STANDARDS

Resistance to single combustion, DSTU EN 60332-1-2

TABLE OF NOMENCLATURES

Article no. Number of cores and
cross section mm2
Maximum
outer diameter
Mass of copper Mass.
40100401 2х2х0,2 6,7 8,6 39
40100402 3х2х0,2 7,2 12,3 52
40100403 2х2х20/7AWG 8,9 22,2 70
40100404 3х2х20/7AWG 9,7 32,8 93