KMRKEEN FRHF FE180/Ek30 (JE-LiHX(St)СH-PF FE180) double twist 2-class flexibility Control and data cable, shielded, flexible, twisted pair, flame retardant
Stability during single burning
Stability when burning in a bundle
Halogen-free
Resistant to electrical influences-shielded
FIELD OF APPLICATION
- Construction, energy, industry, transportation, evacuation, fire extinguishing, smoke removal, emergency power supply and fire warning systems
- For stationary installation in automatic control and monitoring systems of power circuits
- In rooms with dry or humid environments under normal mechanical loads
ADVANTAGES
- Flexible
- Preservation of circuit integrity, under standard temperature conditions, for 30 minutes at temperatures from ~842˚C (Eq30)
- It does not emit corrosive gaseous products in case of fire. gaseous products, which prevents possible damage to electronic equipment
- Pair twisting of the cores reduces crosstalk and mutual interference
- The shields protect the cable from external influences, electrical and magnetostatic effects
- The cables are tested for installation outside the hermetic zone in cable structures and NPP premises in systems of classes: 2, 3, 4 according to the classification of NP 306.2.141-2008
- Additional versions: armored
CONSTRUCTION
|
Resin |
Copper ("l" - tinned) stranded conductors, in accordance with the requirements of DSTU EN 60228, flexibility class 2, 5 or 6 |
|
Insulation |
Organosilicon rubber |
|
Outer shell |
Orange halogen-free polymer composition |
|
Number of cores |
1÷61х2 |
|
Screen 1 |
synthetic film foiled with aluminum + grounding conductor |
|
Screen 2 |
Braid of copper ("el" - tinned) wires |
TECHNICAL CHARACTERISTICS
Electrical resistance depending on the rated area cross-section of the conductor, not more:
mm²
Ohm/km
0,2
110
0,28
67
0,5
36
0,75
24,5
1,0
18,1
1,5
12,1
2,5
7,41
|
Temperature range |
-40˚C to +70˚C |
|
Test voltage |
2000 V (2.5 mm2 - 2500 V) |
|
Operating voltage |
300/500 W |
|
Electrical resistance of insulation |
200 MOhm/km |
|
Minimum bending radius |
7,5 х D |
|
Color identification of cores |
DSTU IEC 60189-2, DIN 47100 |
|
Electrical capacity |
120 pF/m |
COMPLIANCE / STANDARDS
Single combustion - clause 4.1 of DSTU 4809, DSTU EN 60332-1 -2Single combustion - clause 4.1 of DSTU 4809, DSTU EN 60332-1 -2
Combustion in bundles - clause 4.2 of DSTU 4809, DSTU EN 60332-3-22
Toxicity - p. 4.3 DSTU 4809.
Smoke smoke - clause 4.4 of DSTU 4809.
Combustion smoke - clause 4.5 of DSTU 4809, DSTU EN 61034-2.
Halogens and corrosivity - clause 4.6 of DSTU 4809, DSTU EN 60754-2.
Standard temperature conditions (clause 4.7 of DSTU 4809).
Integrity of circuits under conditions of exposure to flame with a temperature of at least 750˚C - 4.8 DSTU 4809, DSTU IEC 60331-21
TABLE OF NOMENCLATURES
| Article no. | Number of cores and cross section mm2 |
Maximum outer diameter |
Mass of copper | Mass. |
|---|---|---|---|---|
| 10437301 | 1х2х0,2 | 11.58 | 37.31 | 142 |
| 10437302 | 2х2х0,2 | 15.25 | 60.52 | 218 |
| 10437304 | 4х2х0,2 | 17.18 | 88.29 | 298 |
| 10437305 | 5х2х0,2 | 18.78 | 104.35 | 352 |
| 10437316 | 1х2х0,5 | 12.17 | 44.07 | 156 |
| 10437317 | 2х2х0,5 | 16.23 | 73.31 | 245 |
| 10437319 | 4х2х0,5 | 18.60 | 111.98 | 350 |
| 10437320 | 5х2х0,5 | 20.10 | 132.44 | 405 |
| 10437323 | 1х2х0,75 | 12.68 | 50.52 | 171 |
| 10437324 | 2х2х0,75 | 17.06 | 85.58 | 271 |
| 10437326 | 4х2х0,75 | 19.60 | 134.25 | 394 |
| 10437327 | 5х2х0,75 | 21.69 | 159.84 | 476 |
| 10437337 | 1х2х1,5 | 13.56 | 62.30 | 196 |
| 10437338 | 2х2х1,5 | 18.74 | 108.84 | 327 |
| 10437340 | 4х2х1,5 | 21.33 | 175.25 | 472 |
| 10437341 | 5х2х1,5 | 23.63 | 210.31 | 572 |
| 10437344 | 1х2х2,5 | 15.03 | 85.76 | 242 |
| 10437345 | 2х2х2,5 | 21.61 | 153.92 | 432 |
| 10437347 | 4х2х2,5 | 24.93 | 259.62 | 651 |
| 10437348 | 5х2х2,5 | 27.58 | 314.27 | 789 |