UNIMATIC® BUS Safety Symmetrical interface cable for BUS systems, shielded, halogen-free
Stability during single burning
Stability when burning in a bundle
Halogen-free
Resistant to electrical influences-shielded
Durability
FIELD OF APPLICATION
- The connections of Foundation Field components are used in the field of process automation, in networks operating according to such standards as RS-232, RS-422, RS-485, Profibus, CAN, LON, etc.
- For towed cable chains
ADVANTAGES
- Consistent and reliable data transmission
- Super flexible application
- High degree of protection against electromagnetic fields
CONSTRUCTION
|
Resin |
Copper conductors in accordance with the requirements of DSTU EN 60228, flexibility class 5 |
|
Insulation |
Polyethylene foam |
|
Outer shell |
Halogen-free yellow composition |
|
Number of cores |
3 |
|
Inner shell |
Halogen-free composition |
|
Screen |
Braid made of tinned copper wires |
TECHNICAL CHARACTERISTICS
Electrical resistance depending on the rated area cross-section of the conductor, not more:
mm²
Ohm/km
0,75 (18/24AWG)
52
|
Temperature range: |
from -40˚С to +70˚С |
|
Test voltage |
3000 В |
|
Operating voltage |
300/500 W |
|
Electrical resistance of insulation |
200 MOhm/km |
|
Minimum bending radius |
7,5 х D |
|
Color identification of cores |
red, green, white |
|
Electrical capacity |
45 pF/m |
|
Wave resistance |
120±10 ohms |
COMPLIANCE / STANDARDS
Resistance to single combustion, DSTU EN 60332-1-2
Resistance to burning in a bundle, DSTU EN 60332-3-22 (cat. A)
Toxicity (low-hazardous - group T1);
Low smoke emission during combustion, DSTU EN 61034-2;
Corrosivity of flue gases, DSTU EN 60754-2
TABLE OF NOMENCLATURES
| Article no. | Number of cores and cross section mm2 |
Maximum outer diameter |
Mass of copper | Mass. |
|---|---|---|---|---|
| 30401001 | 3х0,75 | 9,0 | 42,0 | 111 |