catalog

ПСРкН FRHF FE180/Eк30 (J-HXH-FE180) Communication and alarm wires, fire resistant

ПСРкН FRHF FE180/Eк30 (J-HXH-FE180)
icon_red_1

Stability during single burning

icon_red_2

Stability when burning in a bundle

icon_red_3

Halogen-free

FIELD OF APPLICATION

  • Alarm systems, access control systems, control, monitoring, communication and telecommunication systems, with increased requirements for their fire resistance
  • For the transmission of low-power electrical signals
  • For installation of station equipment, for stationary installation inside buildings, structures, in dry and wet areas, areas with a high concentration of people

ADVANTAGES

  • Preservation of circuit integrity, under standard temperature conditions, from 30 to 90 minutes at temperatures from ~842˚C (Ek30) to ~1006˚C (Ek90)
  • It does not emit corrosive gaseous products in case of fire. gaseous products, prevents possible damage to electronic equipment
  • The wires are tested for laying outside the hermetic zone in cable structures and NPP premises in systems of classes: 2, 3, 4 according to the classification of NP 306.2.141-2008

CONSTRUCTION

Resin

Copper conductors, in accordance with the requirements of DSTU EN 60228, flexibility class 1

Insulation

Organosilicon rubber

Outer shell

Halogen-free composition in orange color

Number of cores

2, 4, 6, 8, 10, 12÷61

TECHNICAL CHARACTERISTICS

Electrical resistance depending on the nominal diameter of the core, not more than:

mm
Ohm/km

0,4
160

0,5
110

0,8
36

1,05
24,5

1,13
18,1

1,38
12,1

1,78
7,41

Temperature range

-30˚С to +70˚С

Test voltage

1000 W

Operating voltage

300 W

Electrical resistance of insulation

100 megohms/km

Minimum bending radius

10 х D

Color identification of cores

DSTU IEC 60304

COMPLIANCE / STANDARDS

Single combustion - clause 4.1 of DSTU 4809, DSTU EN 60332-1 -2Single combustion - clause 4.1 of DSTU 4809, DSTU EN 60332-1 -2

Combustion in bundles - clause 4.2 of DSTU 4809, DSTU EN 60332-3-22

Toxicity - p. 4.3 DSTU 4809.

Smoke smoke - clause 4.4 of DSTU 4809.

Combustion smoke - clause 4.5 of DSTU 4809, DSTU EN 61034-2.

Halogens and corrosivity - clause 4.6 of DSTU 4809, DSTU EN 60754-2.

Standard temperature conditions (clause 4.7 of DSTU 4809).

Integrity of circuits under conditions of exposure to flame with a temperature of at least 750˚C - 4.8 DSTU 4809, DSTU IEC 60331-. 23.

TABLE OF NOMENCLATURES

Article no. Number of cores and
cross section mm2
Maximum
outer diameter
Mass of copper Mass.
10100401 2х0,4 4.3 2.3 14
10100402 4х0,4 5.6 4.61 22
10100403 6х0,4 6.0 6.91 32
10100404 8х0,4 7.3 9.22 39
10100405 10х0,4 7.8 11.52 47
10100406 12х0,4 8.0 13.82 57
10100407 2х0,5 4.5 3.6 18
10100408 4х0,5 6.1 7.2 28
10100409 6х0,5 6.5 10.8 41
10100410 8х0,5 7.8 14.4 51
10100411 10х0,5 8.3 18 62
10100412 12х0,5 8.5 21.6 75
10100413 2х0,8 6.1 9.22 34
10100414 4х0,8 7.8 18.43 53
10100415 6х0,8 8.5 27.65 76
10100416 8х0,8 10.1 36.86 95
10100417 10х0,8 10.8 46.08 118
10100418 12х0,8 11 55.29 141
10100419 2х1,05 6.8 15.88 45
10100420 4х1,05 8.6 31.75 73
10100421 6х1,05 9.4 47.63 106
10100422 8х1,05 11.3 63.5 134
10100423 10х1,05 12.0 79.38 166
10100424 12х1,05 12.4 95.25 201
10100425 2х1,13 7.27 18.39 51
10100426 4х1,13 8.4 36.77 85
10100427 6х1,13 10.15 55.16 122
10100428 8х1,13 10.99 73.55 154
10100429 10х1,13 13.04 91.93 194
10100430 12х1,13 13.69 110.32 231
10100431 2х1,38 8.1 27.42 67
10100432 4х1,38 9.38 54.84 112
10100433 6х1,38 11.34 82.27 162
10100434 8х1,38 12.28 109.69 207
10100435 10х1,38 14.58 137.11 259
10100436 12х1,38 15.28 164.53 309
10100437 2х1,78 9.36 45.62 96
10100438 4х1,78 10.88 91.25 165
10100439 6х1,78 13.18 136.87 239
10100440 8х1,78 14.29 182.49 307
10100441 10х1,78 17.00 228.12 385
10100442 12х1,78 17.78 273.74 458