catalog

КОРкН FRHF FE180/Eк30 (J-HXH-PF FE180) Communication and alarm cable, twisted pair, fire resistant

КОРкН FRHF FE180/Eк30 (J-HXH-PF FE180)
icon_red_1

Stability during single burning

icon_red_2

Stability when burning in a bundle

icon_red_3

Halogen-free

FIELD OF APPLICATION

  • Alarm systems, access control systems, management, control, communication and telecommunication systems
  • For the transmission of low-power electrical signals
  • For installation of station equipment, for stationary installation inside buildings, structures, in dry and wet areas

ADVANTAGES

  • Preservation of circuit integrity, under standard temperature conditions, from 30 to 90 minutes at temperatures from ~842˚C (Ek30) to ~1006˚C (Ek90)
  • Does not emit corrosive gaseous products in fire conditions gaseous products
  • The cables are tested for laying outside the hermetic zone in cable structures and NPP premises in systems of classes 2, 3, 4 according to NP 306.2.141-2008

CONSTRUCTION

Resin

Copper conductors, in accordance with the requirements of DSTU EN 60228, flexibility class 1

Insulation

Organosilicon rubber

Outer shell

Orange halogen-free polymer composition

Number of cores

1÷61х2

TECHNICAL CHARACTERISTICS

Electrical resistance depending on the nominal diameter of the core, not more than:

mm
Ohm/km

0,4
160

0,5
110

0,8
36

1,05
24,5

1,13
18,1

1,38
12,1

1,78
7,41

Temperature range

-30˚С to +70˚С

Test voltage

1500 W

Operating voltage

300 W

Electrical resistance of insulation

100 megohms/km

Minimum bending radius

10 х D

Color identification of cores

DSTU IEC 60304

COMPLIANCE / STANDARDS

Single combustion - clause 4.1 of DSTU 4809, DSTU EN 60332-1 -2Single combustion - clause 4.1 of DSTU 4809, DSTU EN 60332-1 -2

Combustion in bundles - clause 4.2 of DSTU 4809, DSTU EN 60332-3-22

Toxicity - p. 4.3 DSTU 4809.

Smoke smoke - clause 4.4 of DSTU 4809.

Combustion smoke - clause 4.5 of DSTU 4809, DSTU EN 61034-2.

Halogens and corrosivity - clause 4.6 of DSTU 4809, DSTU EN 60754-2.

Standard temperature conditions (clause 4.7 of DSTU 4809).

Integrity of circuits under conditions of exposure to flames with a temperature of at least 750˚С - 4.8 DSTU 4809, DSTU IEC 60331-23

TABLE OF NOMENCLATURES

Article no. Number of cores and
cross section mm2
Maximum
outer diameter
Mass of copper Mass.
10302701 1х2х0,4 4.49 2.38 17
10302702 2х2х0,4 7.48 4.77 32
10302703 3х2х0,4 8.04 7.15 40
10302704 4х2х0,4 8.82 9.54 49
10302705 5х2х0,4 9.68 11.92 57
10302706 6х2х0,4 10.70 14.31 68
10302707 8х2х0,4 11.59 19.08 83
10302708 10х2х0,4 13.92 23.85 108
10302709 14х2х0,4 15.14 28.62 124
10302710 20х2х0,4 17.80 47.70 181
10302711 1х2х0,5 4.97 3.88 21
10302712 2х2х0,5 8.56 7.75 41
10302713 3х2х0,5 9.08 11.63 52
10302714 4х2х0,5 10.09 15.51 65
10302715 5х2х0,51 11.10 19.38 77
10302716 6х2х0,51 12.14 23.26 89
10302717 8х2х0,51 13.30 31.02 112
10302718 10х2х0,51 15.73 38.77 138
10302719 14х2х0,51 17.27 46.52 164
10302720 20х2х0,51 20.36 77.54 243
10302721 1х2х0,8 5.98 9.54 33
10302722 2х2х0,8 10.47 19.08 65
10302723 3х2х0,8 11.12 28.62 84
10302724 4х2х0,8 12.26 38.16 104
10302725 5х2х0,8 13.64 47.70 127
10302726 6х2х0,8 14.95 57.24 148
10302727 8х2х0,8 16.49 76.32 193
10302728 10х2х0,8 19.55 95.40 238
10302729 14х2х0,8 21.57 114.48 287
10302730 20х2х0,8 25.46 190.79 434
10302731 1х2х1,05 6.90 16.43 46
10302732 2х2х1,05 12.08 32.87 89
10302733 3х2х1,05 12.97 49.30 120
10302734 4х2х1,05 14.31 65.73 150
10302735 5х2х1,05 15.93 82.17 184
10302736 6х2х1,05 17.48 98.60 216
10302737 8х2х1,05 19.26 131.47 281
10302738 10х2х1,05 22.89 164.33 347
10302739 14х2х1,05 25.35 197.20 424
10302740 20х2х1,05 29.96 328.67 649
10302741 1х2х1,38 8.00 28.39 66
10302742 2х2х1,38 14.17 56.77 129
10302743 3х2х1,38 15.21 85.16 176
10302744 4х2х1,38 16.81 113.55 222
10302745 5х2х1,38 18.71 141.93 273
10302746 6х2х1,38 20.56 170.32 321
10302747 8х2х1,38 22.64 227.09 419
10302748 10х2х1,38 26.96 283.86 519
10302749 14х2х1,38 29.71 340.64 625
10302750 20х2х1,38 35.20 567.73 973