catalog

КМРкHс FRHF FE180/Eк90 (LIНХН-FE180) Power cable, flexible, fire-resistant

КМРкHс FRHF FE180/Eк90 (LIНХН-FE180)
icon_red_1

Stability during single burning

icon_red_2

Stability when burning in a bundle

icon_red_3

Halogen-free

FIELD OF APPLICATION

  • Construction, energy, industry, transportation facilities in evacuation, fire extinguishing, smoke removal, emergency power supply and fire warning systems
  • For fixed installation in power and lighting networks
  • In rooms with dry or humid environments under normal mechanical loads

ADVANTAGES

  • Preservation of circuit integrity, under standard temperature conditions, from 30 to 90 minutes at temperatures from ~842˚C (Ek30) to ~1006˚C (Ek90)
  • Does not emit corrosive gaseous products in fire conditions gaseous products
  • The cables are used for laying outside the hermetic zone in cable structures and NPP premises in systems of classes 2, 3, 4 according to NP 306.2.141-2008

CONSTRUCTION

Resin

Copper conductors, in accordance with the requirements of DSTU EN 60228, flexibility class 1 or 2

Insulation

Organosilicon rubber

Outer shell

Halogen-free composition in orange color

Number of cores

2, 3, 4, 5

TECHNICAL CHARACTERISTICS

Electrical resistance depending on the rated area cross-section of the conductor, not more:

mm²
Ohm/km

0,5
36

1,0
18,1

1,5
12,1

2,5
7,41

4
4,61

6
3,08

10
1,83

16
1,15

25
0,727

35
0,524

Temperature range

-40˚C to +80˚C

Test voltage

2500 W

Operating voltage

300/500 W

Electrical resistance of insulation

100 megohms/km

Minimum bending radius

12 х D

Color identification of cores

DSTU HD 308 S2

COMPLIANCE / STANDARDS

Single combustion - clause 4.1 of DSTU 4809, DSTU EN 60332-1 -2Single combustion - clause 4.1 of DSTU 4809, DSTU EN 60332-1 -2

Combustion in bundles - clause 4.2 of DSTU 4809, DSTU EN 60332-3-22

Toxicity - p. 4.3 DSTU 4809.

Smoke smoke - clause 4.4 of DSTU 4809.

Combustion smoke - clause 4.5 of DSTU 4809, DSTU EN 61034-2.

Halogens and corrosivity - clause 4.6 of DSTU 4809, DSTU EN 60754-2.

Standard temperature conditions (clause 4.7 of DSTU 4809).

Integrity of circuits under conditions of exposure to flame with a temperature of at least 750 ° C - clause 4.6 of which is at least 750 ° C - 4.8 DSTU 4809, DSTU IEC 60331-21

TABLE OF NOMENCLATURES

Article no. Number of cores and
cross section mm2
Maximum
outer diameter
Mass of copper Mass.
11303801 2х0,5 6.6 9.21 38
11303802 3х0,5 6.9 13.82 48
11303803 4х0,5 7.7 18.43 62
11303804 5х0,5 8.3 23.03 74
11303805 2х0,75 7.2 13.82 49
11303806 3х0,75 7.4 20.73 64
11303807 4х0,75 8.3 27.64 81
11303808 5х0,75 9.1 34.55 97
11303809 2х1,0 8.1 18.43 59
11303810 3х1,0 8.6 27.64 77
11303811 4х1,0 9.6 36.85 102
11303812 5х1,0 10.4 46.06 122
11303813 2х1,5 8.7 27.64 74
11303814 3х1,5 9.2 41.46 98
11303815 4х1,5 10.4 55.28 133
11303816 5х1,5 11.4 69.10 162
11303817 2х2,5 10.1 46.06 101
11303818 3х2,5 11.0 69.10 142
11303819 4х2,5 12.2 92.13 186
11303820 5х2,5 13.4 115.16 225
11303821 2х4,0 12.2 73.70 152
11303822 3х4,0 13.2 110.55 204
11303823 4х4,0 14.6 147.41 260
11303824 5х4,0 16.6 184.26 333
11303825 2х6,0 13.9 110.55 199
11303826 3х6,0 14.7 165.83 273
11303827 4х6,0 16.8 221.11 367
11303828 5х6,0 18.5 276.39 446
11303829 2х10 16.8 184.26 311
11303830 3х10 18.9 276.39 429
11303831 4х10 20.3 368.51 551
11303832 5х10 23.3 460.64 691
11303833 2х16 19.6 294.81 444
11303834 3х16 21.3 442.22 623
11303835 4х16 24.5 589.62 824
11303836 5х16 27.2 737.03 1010
11303837 2х25 24.0 460.64 673
11303838 3х25 26.4 690.96 948
11303839 4х25 29.4 921.28 1231
11303840 5х25 33.2 1151.60 1523
11303841 2х35 27.5 644.90 886
11303842 3х35 29.5 967.35 1261
11303843 4х35 33.3 1289.80 1643
11303844 5х35 37.1 1612.25 2037