catalog

H07V-K Installation wire

H07V-K
icon_red_1

Stability during single burning

FIELD OF APPLICATION

  • In lighting and power networks, during the installation of electrical equipment, machinery, mechanisms and machine tools
  • For connecting installations, signaling devices, electronic components in devices, enclosures, cabinets

ADVANTAGES

  • Saves time during installation
  • High flexibility

CONSTRUCTION

Resin

Copper conductors in accordance with the requirements of DSTU EN 60228, flexibility class 5

Insulation

Polyvinyl chloride plastic.

Number of cores

1

TECHNICAL CHARACTERISTICS

Electrical resistance depending on the rated area cross-section of the conductor, not more:

mm²
Ohm/km

1,5
13,3

2,5
7,98

4
4,95

6
3,3

10
1,91

16
1,21

25
0,78

35
0,554

Temperature range:
-in fixed installation
-conditions during installation

-40˚С to +80˚С
-5˚С to +70˚С

Test voltage

2000 В

Operating voltage

450/750 V

Electrical resistance of insulation

10 MOhm/km

Minimum bending radius

10 х D

Color identification of cores

DSTU IEC 60227-1

COMPLIANCE / STANDARDS

DSTU EN 50525-2-31

Resistance to single combustion, DSTU EN 60332-1-2

TABLE OF NOMENCLATURES

Article no. Number of cores and
cross section mm2
Maximum
outer diameter
Mass of copper Mass.
50200401 1.5 3.4 13.33 21.15
50200402 2.5 4.1 22.21 33.48
50200403 4 4.8 35.82 49.06
50200404 6 5.3 53.74 69.30
50200405 10 6.8 90.98 116.02
50200406 16 8.1 145.57 175.65
50200407 25 10.2 222.90 274.67
50200408 35 11.7 318.43 376.42