catalog

КОРкНс FRHF FE180/Eк30 (НХН-FE180) Power cable, fire resistant

КОРкНс FRHF FE180/Eк30 (НХН-FE180)
icon_red_1

Stability during single burning

icon_red_2

Stability when burning in a bundle

icon_red_3

Halogen-free

FIELD OF APPLICATION

  • Construction, energy, industry, transportation facilities in evacuation, fire extinguishing, smoke removal, emergency power supply and fire warning systems
  • For fixed installation in power and lighting networks
  • In rooms with dry or humid environments under normal mechanical loads

ADVANTAGES

  • Preservation of circuit integrity, under standard temperature conditions, from 30 to 90 minutes at temperatures from ~842˚C (Ek30) to ~1006˚C (Ek90)
  • Does not emit corrosive gaseous products in fire conditions gaseous products
  • The cables are used for laying outside the hermetic zone in cable structures and NPP premises in systems of classes 2, 3, 4 according to NP 306.2.141-2008

CONSTRUCTION

Resin

Copper conductors, in accordance with the requirements of DSTU EN 60228, flexibility class 1 or 2

Insulation

Organosilicon rubber

Outer shell

Halogen-free composition in orange color

Number of cores

2, 3, 4, 5

TECHNICAL CHARACTERISTICS

Electrical resistance depending on the rated area cross-section of the conductor, not more:

mm²
Ohm/km

0,5
36

1,0
18,1

1,5
12,1

2,5
7,41

4
4,61

6
3,08

10
1,83

Temperature range

-40˚C to +80˚C

Test voltage

2500 W

Operating voltage

300/500 W

Electrical resistance of insulation

100 megohms/km

Minimum bending radius

15 х D

Color identification of cores

DSTU HD 308 S2

COMPLIANCE / STANDARDS

Single combustion - clause 4.1 of DSTU 4809, DSTU EN 60332-1 -2Single combustion - clause 4.1 of DSTU 4809, DSTU EN 60332-1 -2

Combustion in bundles - clause 4.2 of DSTU 4809, DSTU EN 60332-3-22

Toxicity - p. 4.3 DSTU 4809

Smoke smoke - clause 4.4 of DSTU 4809.

Combustion smoke - clause 4.5 of DSTU 4809, DSTU EN 61034-2.

Halogens and corrosivity - clause 4.6 of DSTU 4809, DSTU EN 60754-2.

Standard temperature conditions (clause 4.7 of DSTU 4809).

Integrity of circuits under conditions of exposure to flame with a temperature of at least 750 ° C - clause 4.6 of which is at least 750 ° C - 4.8 DSTU 4809, DSTU IEC 60331-21

TABLE OF NOMENCLATURES

Article no. Number of cores and
cross section mm2
Maximum
outer diameter
Mass of copper Mass.
11303301 2х0,5 6.0 9.21 38
11303302 3х0,5 6.4 13.82 48
11303303 4х0,5 7.0 18.43 62
11303304 5х0,5 7.8 23.03 74
11303305 2х0,75 6.8 13.82 49
11303306 3х0,75 7.2 20.73 64
11303307 4х0,75 8.0 27.64 81
11303308 5х0,75 8.8 34.55 97
11303309 2х1,0 7.4 18.43 59
11303310 3х1,0 7.8 27.64 77
11303311 4х1,0 9.0 36.85 102
11303312 5х1,0 9.9 46.06 122
11303313 2х1,5 8.2 27.64 74
11303314 3х1,5 8.7 41.46 98
11303315 4х1,5 10.0 55.28 133
11303316 5х1,5 10.9 69.10 162
11303317 2х2,5 9.6 46.06 101
11303318 3х2,5 10.4 69.10 142
11303319 4х2,5 11.7 92.13 186
11303320 5х2,5 12.9 115.16 225
11303321 2х4,0 11.6 73.70 152
11303322 3х4,0 13.2 110.55 204
11303323 4Х4,0 14.6 147.41 260
11303324 5х4,0 16.6 184.26 333
11303325 2х6,0 13.1 110.55 199
11303326 3х6,0 14.6 165.83 273
11303327 4х6,0 16.8 221.11 367
11303328 5х6,0 18.5 276.39 446