SiD Heat resistant wire
Stability during single burning
Heat resistant +180 °C
FIELD OF APPLICATION
- In high and low ambient temperatures
- In the installation of electrical distribution cabinets, instrumentation, apparatus, electric motors, saunas and solariums, thermoelectric elements, electrical elements, furnace production and plastic processing
- In the steel industry, aviation, shipbuilding, ceramics, glass and cement plants
- At power plants and in electric power plants
ADVANTAGES
- Absence of halogen-containing substances in materials
- High operating temperature
- Resistance to high molecular weight oils, animal and vegetable fats, alcohols, plasticizers, dilute acids, alkaline and salt solutions, oxidizing agents, fresh water, as well as to tropical conditions
CONSTRUCTION
|
Resin |
Copper conductors are tinned in accordance with the requirements of DSTU EN 60228, flexibility class 1 |
|
Insulation |
Brown silicone rubber |
|
Number of cores |
1 |
TECHNICAL CHARACTERISTICS
Electrical resistance depending on the rated area cross-section of the conductor, not more:
mm²
Ohm/km
0,5
36
1
18,1
1,5
12,1
2,5
7,41
4
4,61
6
3,08
10
1,83
|
Temperature range: |
from -60˚С to +180˚С |
|
Test voltage |
2000 В |
|
Operating voltage |
300/500 W |
|
Electrical resistance of insulation |
200 MOhm/km |
|
Minimum bending radius limited mobility fixed application |
15 х D |
|
Color identification of cores |
DSTU HD 308 S2 |
COMPLIANCE / STANDARDS
Resistance to single combustion, DSTU EN 60332-1-2
Corrosion activity, DSTU EN 60754-2
TABLE OF NOMENCLATURES
| Article no. | Number of cores and cross section mm2 |
Maximum outer diameter |
Mass of copper | Mass. |
|---|---|---|---|---|
| 11000101 | 1х0,5 | 2.0 | 4.47 | 9.2 |
| 11000102 | 1х1 | 2.53 | 8.92 | 16.1 |
| 11000103 | 1х1,5 | 2.98 | 13.30 | 23.1 |
| 11000104 | 1х2,5 | 3.58 | 22.12 | 35.7 |
| 11000105 | 1х4 | 4.25 | 35.35 | 53.6 |
| 11000106 | 1х6 | 4.76 | 53.19 | 74.3 |
| 11000107 | 1х10 | 5.77 | 88.99 | 117.9 |