Li2YCY Mounting wire, shielded
Stability during single burning
Resistant to electrical influences-shielded
FIELD OF APPLICATION
- In lighting and power networks, during the installation of electrical equipment, machinery, mechanisms and machine tools
- For connecting installations, signaling devices, electronic components in devices, enclosures, cabinets
ADVANTAGES
- Saves time during installation
- The presence of a shield protects against electromagnetic waves
CONSTRUCTION
|
Resin |
Copper conductors in accordance with the requirements of DSTU EN 60228, flexibility class 5 |
|
Insulation |
Polyethylene |
|
Outer shell |
Polyvinyl chloride plastic |
|
Number of cores |
1 |
|
Screen |
Braid made of tinned copper wires |
TECHNICAL CHARACTERISTICS
Electrical resistance depending on the rated area cross-section of the conductor, not more:
mm²
Ohm/km
0,14
125
0,25
84
0,5
39
0,75
19,5
1
19,5
|
Temperature range: |
from -40˚С to +80˚С |
|
Test voltage |
2000 В |
|
Operating voltage |
300/500 W |
|
Electrical resistance of insulation |
10 MOhm/km |
|
Minimum bending radius |
10 х D |
|
Color identification of cores |
DSTU IEC 60227-1 |
COMPLIANCE / STANDARDS
Resistance to single combustion, DSTU EN 60332-1-2
TABLE OF NOMENCLATURES
| Article no. | Number of cores and cross section mm2 |
Maximum outer diameter |
Mass of copper | Mass. |
|---|---|---|---|---|
| 50200201 | 0.14 | 2.91 | 5.1 | 15.40 |
| 50200202 | 0.25 | 3.20 | 7.0 | 18.71 |
| 50200203 | 0.5 | 3.52 | 10.2 | 24.88 |
| 50200204 | 0.75 | 3.88 | 13.5 | 30.22 |
| 50200205 | 1 | 4.12 | 16.5 | 34.44 |